                      Magnetics Components That Match 1,500-V Battery Energy Storage System Requirements









                                                                                     1.  DC breaker, contactor, and/or switch
                                                                                       disconnector
                                                                                     2. CMS battery monitoring
                                                                                     3.  Main DC breaker, contactor, and/or
                                                                                       switch disconnector
                                                                                     4. DC SPD
                                                                                     5. Power supply monitoring relay
                                                                                     6. AC main breaker and RCD
                                                                                     7. AC contactor
                                                                                     8. Insulation monitor



           Figure 2: Exploded view of energy storage



           transformer is UL-listed, which provides   voltage while providing the necessary match-  need to be rated to a different category.
           assurance of design safety.         ing and common-mode noise removal so that   These categories determine the level of
             As Figure 4 shows, this 1,500-V signal   the communications between the monitoring   surge testing that is required during qual-
           transformer isolates and protects the battery   ICs and the central management board are   ification. Surge tests are used primarily to
           management system (BMS) board isoSPI™   also secure and uninterrupted. In addition,   check that there is adequate clearance so that
           interface. It is important to note that the BMS   the features of the Model SM91527L trans-  if an event such as a lightning strike were
           interface is operating in a non-hazardous   former allow it to still meet isoSPI™ driver   to occur, the gap between the windings on
           environment separate from the battery pack   recommendations in terms of insertion loss   the transformer would not break down and
                                               (max 1.2 dB at 4 MHz) and EMI (–50-dB,    ionize, causing a crossover. To be rated at
                                               1- to 100-MHz CMRR).                1,500 V for an overvoltage Category II up to
                                                                                   a 5,000-meter altitude, the reinforced trans-
                                               INSULATION REQUIREMENTS FOR         former must be able to withstand an impulse
                                               TRANSFORMERS RATED TO 1,500 V       test of 12 kV peak.
                                               Transformers with reinforced insulation up to   Another series of tests are mandatory for
                                               1,500 V must pass tests as defined by    checking the quality of the insulation mate-
                                               IEC 60664 to demonstrate that the insulation   rial itself. Reinforced insulation is checked by
                                               will survive sudden surges, which could hap-  applying a DC or AC voltage between the pri-
                                               pen on the electricity grid or on the battery   mary and secondary side and measuring the
                                               pack itself. One of the factors to consider is   amount of leakage current between the two
                                               the type of application. Consumer equipment   sides. This is also known as a dielectric test,
                                               will have a particular overvoltage category   as the permittivity of the insulation material
           Figure 3: Model SM91527L            requirement, while industrial equipment may   will accumulate charge, which translates into


























           Figure 4: Block diagram showing the connection of the isoSPI™ bus between master and slave